General
In the following the device will be referred to as the
movement detector.
The movement block will only switch off when there is
no more movement in front of the device - in other
words, independently of the brightness.
The ETS application includes 5 independent
movement blocks, each with 4 output objects.
|
Note:
All of the settings described refer to ETS version
3, but you can also use all the settings and
functions with ETS version 2.
The application files (vd2 and vd3) are
configured in such a way that the application
loading time is considerably reduced. When you
convert an ETS 2 project to ETS 3, you lose this
time saving. If you are working with ETS 3, use
the vd3 files.
Total possible addresses and connections:
254 addresses; 255 connections
|
Note:
If you switch back to the preset values in either
ETS 2 or ETS 3 (by clicking "Standard"), all the
values that you have changed so far will be
deleted. Any group addresses which have been
parametrised will be lost.
|
Note:
Due to the fact that various functions depend
on other functions, these dependent functions
will not be visible and selectable in the ETS
unless the preceding function has been
enabled. If you de-select functions or change
parameters, group addresses that have already
been connected may be removed.
Getting started quickly
When you insert the application in the ETS or click on
the "Standard" button, the ETS application will switch
automatically to minimum configuration.
In minimum configuration, it is possible to put the
presence detector into operation. For some
application cases, the minimum configuration is even
adequate for practical use. We also recommend
opening minimum configuration as a way of
familiarising yourself with the application software for
the presence detector. Here all of the extended or
more complex parameters are disabled. In "Block
configuration" only the first "Movement" block is
enabled for use. In the "Telegrams" tab only output
object 1 is enabled. This is a 1-bit output object. At the
start of movement this object sends a 1 telegram and
when the internal staircase timer has elapsed it sends
a 0 telegram. Each parameter can always be tuned to
its individual requirements. The brightness threshold
and the staircase timer always need to be adjusted to
suit requirements. Check the "Brightness" and "Times"
tabs.
In this way the corresponding objects are connected
to a KNX switch actuator.
To familiarise yourself with the extended and more
complex parameters see the following pages.
General functions
The common safety pause
The application has a common safety pause system -
in other words, a safety pause triggered by the
movement detector will affect all blocks in the
application. As specified in a parameter the safety
pause can be triggered at the status feedback object
(safety pause) when there is an OFF telegram or when
there is an OFF and ON telegram.
The status feedback object of the switching/dimming
actuator must be connected to the feedback safety
pause object of the movement detector.
Once a safety pause has been started, signals from
the movement sensor will no longer be evaluated for
this period of time. An elapsed staircase timer cannot
be started by a movement during an active safety
pause and an ongoing staircase timer cannot be
retriggered by a movement.
An ongoing staircase timer is not affected by a safety
pause being activated. In other words, the staircase
timer will run through in the usual way.
|
Note:
Optical feedback can only be avoided by
selecting the right installation location for the
movement detector and the lighting. The safety
pause system and the safety pause object of
the application cannot compensate for all
planning mistakes.
Communication objects
You can select the following communication objects:
General:
Movement/monitoring 1307/1.0
Function Object name Type Prio Flags Behaviour
Safety
pause
Status feedback
object
1 bit Low WC Receive
1/1/1
1/1/2
Switch object
Status feedback obj.
Switch
Actuator
Status feedback obj.
Safety pause
Movement
Detector
Switch object
5